ICS
Intelligent Control Systems
Facility Automation and Security System Specialist
Facility Automation and Security Systems
Duct/Outdoor Temperature & Humidity Transmitter Model H2, 3, 4N
Application and Features
-
Humidity and temperature transmitters H2N (duct), H3N (outside) and H4N (remote) are designed for environment monitoring and controlling in industrial and commercial buildings
-
High performance digital sensors and circuits, ensure accurate measurement and temperature compensation
-
Digital technology applied, multiple outputs optional, over voltage and reverse polarity protection, high reliability and anti-interference capability
-
LCD display temperature and humidity alternatively
-
LCD & function keys can set parameters and calibrate output, so the product can be a stand alone controller
-
Good long term stability and reliability
-
100% field changeable sensor without re-calibration
-
Fast response
-
High protection rate up to IP65
Specification
Relative Humidity Sensor: Digital polymer
Range: 0~100%RH
Output: see models
Accuracy: 2%, 3%, (25°C, 20~80%RH)
Hysteresis: <±1%RH Response time: <10s (25°C, in slow
air) Drift: <±0.5%RH / year
Temperature Sensor: Digital temperature sensor or RTD/thermistor Range: 0~50°C, 0~100°C, -40~60°C, or others
Output: 4~20mA (2wires), 0~10VDC (3wires),
RS485/Modbus, or RTD/thermistor: see Models
and resistance table
Accuracy: transmitter: =±0.4°C @ 5~60°C or 0.3°C @ 5~60°C RTD or thermistor: typical 0.2~0.5°C@ 25°C, see models
Power: Current: 18.5~35VDC (RL=500O); 8.5~35VDC (RL=0O)
Voltage: 16~28VAC/ 16~35VDC Output Load: =500O (current), =2KO (voltage)
Relay output: 2×SPST, 3A/30VDC, 3A/250VAC
Display and keys: 4 digits LCD, with unit indication,backlight (4- 20mA N/A), 3 touch keys, see more details on LCD & Keys operation
Work Temp.: -30~70°C (LCD: -20~70°C), 5~95%RH (Non
cond.)
Housing: ABS housing, UHMW-PE filter (H2/H4N), SS
probe and sintered filter (H3N)
Protection: IP65
Weight: H2N:360g; H3N:270g; H4N:430g
Approval: CE