Differential Air Pressure switch Model 606
Application and Features
-
Monitoring overpressure, vacuum and differential pressure of the air and other non-combustible, non-aggressive gases
Specification
Adjustable range: 4 ranges, see models
Pressure limit: 7500Pa (-30~75°C)
Working temperature: -30~75°C
Storage temperature: -30~75°C
Pressure connection: f6.0mm plastic tube, P1 or “+” high and “-” low
pressure
Service life: over 1,000,000 switching cycles
Electrical Contact: SPDT, 1.5A/ 250VAC, 0.2A/30VDC
Max. switching frequency: 6 switching cycles/min
Electrical connection: Flag or screw terminals
Repeatability: ±2%
Materials: housing PC, diaphragm silicone and silver
alloy/gold plated contact
Weight: 135g with bracket, 85g without bracket
Protection: IP54